In what environment should air cooled water chiller system be installed?

ClassificationIndustry News 159

In what environment should air cooled water chiller system be installed?

1. Installation requirements of LC -25°C ~ -5°C Low Temperature Chillers.

(1) The unit shall avoid approaching fire sources and inflammables. If it is installed together with boiler and other heating elements, full attention shall be paid to the influence of thermal radiation.

(2) Choose a well-ventilated place with room temperature below 45 ℃. It is not allowed to install and store outdoors or in the environment with corrosive gas.

(3) Places with less dust shall be selected.

(4) The site shall be well lit for maintenance and inspection.

(5) To meet the needs of maintenance, repair and cleaning of evaporator and condenser heat exchange tubes. There must be enough pipe extraction space at either end of the unit, and the length direction should be equal to the length of the evaporator and condenser of the unit.

(6) In order to facilitate the lifting and maintenance of the machine, the space required for the installation, operation and maintenance of the unit shall be reserved.

(7) Complete drainage shall be realized around the unit and the whole machine room.

2. Installation procedure of air-cooled water chiller.

The installation site of the unit must be the floor, installation pad or base storage, with the levelness within 6.4mm, and can bear the operating weight of the unit. The unit shall be placed in the machine room with a room temperature of 4.4-40 ℃, and there shall be enough space around and above the unit for daily maintenance. At one end of the unit, the extraction space for cleaning the condenser tube bundle shall be reserved, and the door hole or other suitable holes can also be used.

The water pipe with the pipe diameter of the cooling system and cold water system suitable for the maximum power operation of the unit shall be connected correctly. For ordinary applications, the water flow velocity through the evaporator and condenser is allowed to be between 1.0-3.6m/s.

3. Environmental precautions for air-cooled water chillers.

Make sure that the configuration of the control panel and power supply are in the proper environmental conditions. It is necessary to select the appropriate installation environment according to your application requirements. Avoid high temperature environment during installation, because it will suffocate the environment.

Copyright information belongs to lneya-online.com, please contact email for details: lilia@lneya.com

Or scan the WhatsApp or WeChat QR code below to contact us. 

WhatsAPP                                   WeChat

scan

Previous: Next:
Get Free Quote Plan

loading...

购物车

X

我的足迹

X
keywords:< a href="https://lneya-online.com/sitemap.html" title="water chiller"target="_blank">Bottled joy < a href="https://lneya-online.com/sitemap.xml" title="water chiller"target="_blank">water chiller