Reasons and Solutions for the Poor Cooling Effect of the Chiller
1. Whether the refrigerant leaks
Cause analysis: The refrigerant leaks in the industrial chiller system, and the cooling capacity is insufficient. When the suction and discharge pressures are low, the expansion valve will have intermittent sound of airflow.
Solution: If the refrigerant leaks, please do not rush to add the refrigerant. The leak point should be found immediately, and the refrigerant should be added after repair.
2. Excessive refrigerant addition after maintenance
Reason analysis: If the refrigerant is added too much, it will occupy a certain volume of the condenser, reduce the heat dissipation area, and reduce the cooling efficiency.
Solution: It is necessary to discharge the excess refrigerant at the high-pressure shut-off valve after the industrial chiller is stopped for a few minutes.
3. There is air in the refrigeration system
Reason analysis: Air in the chiller refrigeration system will reduce the refrigeration efficiency. The prominent phenomenon is that the suction and exhaust pressures increase, the temperature from the compressor outlet to the condenser inlet increases significantly, there is air in the system, and the exhaust pressure, Exhaust temperature will increase.
Solution: It is necessary to release the air at the high-pressure shut-off valve after stopping the industrial chiller for a few minutes.
4. Low compressor efficiency
Reason analysis: The compressor in the chiller that has been used for a long time has large wear and tear, the gap between each component is large, and the sealing performance of the air valve decreases, resulting in a decrease in the exhaust volume.
Solution: Check whether the compressor cylinder head paper gasket is broken down and causes leakage. Check whether the high-pressure and low-pressure exhaust valves are not tightly closed. Check the fit clearance between the piston and the cylinder.
5. The frost on the evaporator surface is too thick
Reason analysis: The evaporator used for a long time needs to be defrosted regularly. If it is not defrosted, the frost on the evaporator pipeline will accumulate and thicken. When the entire pipeline is wrapped into a transparent ice layer, it will seriously affect the heat transfer effect.
Solution: stop defrosting.
6. Filter clogged
Analysis of the cause: The desiccant has been used for a long time to form a paste to seal the filter, or the dirt gradually accumulated in the filter to cause blockage.
Solution: Remove the filter for cleaning.
Somos un fabricante profesional de equipos de control de temperatura, el apoyo a los servicios personalizados, por favor consúltenos para más detalles
Refrigeradores de baja temperatura
Rango de control de temperatura: -150°C a -5°C
Application: Various Reactors, Distillation or Extraction System, Laboratory, Research Institute, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Semiconductor Test, Aerospace, Biological and Other Industries.
Temperatura | Serie -25°C ~ -5°C | Serie -45°C ~ -10°C | Serie -60°C ~ -10°C | Serie -80°C ~ -30°C | Serie -110°C ~ -50°C | Serie -150°C ~ -110°C |
Capacidad de refrigeración | hasta 360 kW | hasta 360 kW | hasta 360 kW | hasta 270 kW | hasta 180 kW | hasta 11 kW |
Enfriadoras de recirculación
Temperature Control Range: -120°C to 30°C
Application: Various Reactors, Distillation or Extraction System, Laboratory, Research Institute, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Semiconductor Test, Aerospace, Biological and Other Industries.
Temperatura | -25°C ~ 30°C series | -45°C ~ 30°C series | Serie -60°C ~ -20°C | Serie -80°C ~ -20°C | Serie -120°C ~ -70°C |
Capacidad de refrigeración | hasta 38 kW | hasta 12 kW | hasta 7,2 kW | hasta 7,2 kW | hasta 8,6 kW |
Normal Temperature Chillers
Rango de control de temperatura: +5°C a +50°C
Application: Various Reactors, Distillation or Extraction System, Laboratory, Research Institute, Chemical, Pharmaceutical, Petrochemical, Biochemical, Medical, Hospital, R&D Workshop, Semiconductor Test, Aerospace, Biological and Other Industries.
Temperatura | -18°C ~ +30°C | +5°C ~ +50°C series |
Capacidad de refrigeración | hasta 0,9 kW | hasta 50 kW |