検索 すべて検索

Why is the compressor in the air cooled industrial chiller refrigerator overloaded?

分類業界ニュース 143

Why is the compressor in the air cooled industrial chiller refrigerator overloaded?

(1) The cause of compressor overload failure of GX/GY -65°C ~ -10°C 産業用冷蔵庫:

1. Check whether there is refrigerant leakage at the copper pipe welding interface in the refrigerator.

2. Observe whether there is ventilation around the refrigerator.

3. Check whether the dust screen and condenser of the refrigerator are blocked by dust.

4. Whether the refrigerator fan works normally.

5. Check whether the refrigerator voltage is normal.

6.コンプレッサーの始動静電容量が正常値の範囲内かどうか;

7. Whether the cooling capacity of the refrigerating machine is less than the load heat.

8.コンプレッサーに故障があり、作動電流が高すぎ、作動時に異音がする;

(2) Solution to overload of air-cooled industrial refrigerator compressor:

1.冷媒漏れによる油汚れがあります。注意して観察してください。冷媒漏れが発生した場合は、アフターサービス担当者にご連絡ください;

2. The distance between the refrigerator air outlet (fan) and the obstacle shall be more than 50cm, and the distance between the refrigerator air inlet (dust screen) and the obstacle shall be more than 30cm (the distance between the air outlet behind the refrigerator and the obstacle shall be more than 30cm), and the distance between the side air inlet and the obstacle shall be more than 8cm);

3.機械の使用環境に応じて定期的に除塵を行う;

4.コンプレッサーが始動すると、ファンも同期して始動する。ファンが始動しない場合は、ファンが故障していないか確認してください;

5.機械の銘板に記載されている電圧と周波数を供給してください。電圧変動が大きい場合は、電圧レギュレータの設置を推奨します。

6.マルチメータで静電容量を測定し、静電容量面が損傷していないか確認する;

7. Select and prepare refrigerators with cooling capacity greater than calorific value.

8.メーカーに連絡し、同じモデルのコンプレッサーを交換する;