The Reasons for the High Pressure Failure of the Chiller

KlassifizierungIndustrie-Nachrichten 448

 

The Reasons for the High Pressure Failure of the Chiller

 

In the industrial production process, the chiller plays the role of low-temperature refrigeration, providing temperature control for production equipment such as coating machines, injection molding machines, sand mills, and reaction kettles.

Generally speaking, there are many low temperature chillers and normal temperature chillers. The normal temperature chillers are generally within 0°C to 30°C, and the low temperature chillers are generally around -150°C to 0°C. Below we will explain to you several reasons for the high pressure failure of industrial chillers.

1. Insufficient cooling water flow

This situation mostly occurs in the type of water-cooled chiller equipment, because the air-cooled chiller relies on the fan to dissipate heat by itself. The cooling water is mainly used to cool the chiller equipment, and it is usually circulated to the cooling tower for heat dissipation. If the high pressure of the chiller occurs, the reason may be that the water pump is damaged, the pressure of the cooling water pumped by the water pump is too low, the pipe of the filter is blocked, and so on. If the cooling water flow is insufficient, you should also check whether the pipes in the cooling water circulation system are broken and whether there is water leakage. This is the direct cause of insufficient cooling water flow, which can be identified and judged by the naked eye.

2. The cooling water temperature is too high, resulting in poor condensation effect

Especially for water-cooled chillers, its cooling water circulation system includes circulating water pumps, circulating water cooling water pipes, and cooling towers.

Any problem with any component in the system may cause the temperature of the cooling water to be too high and lead to the high pressure of the final equipment, which is mainly reflected in the failure of the cooling tower, the failure of the fan, and the water distributor.

3. Condenser scaling or blockage

As one of the four major refrigeration components of the chiller, the condenser usually affects the working effect of the condenser through the water quality of the condenser. For example, the water is mixed with dust impurities. It will cause the condenser to become dirty and clogged. Its heat exchange area becomes smaller and the efficiency becomes lower, which will affect the water flow. Generally, it can be treated by chemical cleaning and descaling.

4. Refrigerant problem

Refrigerant is the medium for refrigerant circulation in the refrigerant system. Too much refrigerant in the chiller will cause high suction and exhaust pressure and balance pressure.

5. False alarm caused by electrical fault

For example, the relay protector is wet, the contact is poor or damaged, the chip electronic board is damp or damaged, and the communication failure will also cause false alarms of electrical faults.

By manually measuring the operating current and discharge pressure of the compressor, both are within the normal range, which can indicate that the false alarm is caused by the electrical system.

Therefore, we must pay attention to measuring the various operating parameters of the chiller, and find and deal with the fault in time. To deal with the high-pressure failure of the chiller, it is necessary to find a regular manufacturer or a professional third-party maintenance company, so as to avoid more serious losses due to the mistakes of the maintenance workers.

Wir sind ein professioneller Hersteller von Temperaturkontrollgeräten und unterstützen kundenspezifische Dienstleistungen, bitte uns konsultieren für Details!

 


Low Temperature Water Cooled Chillers

Temperaturregelbereich: -150°C bis -5°C

Anwendung: Verschiedene Reaktoren, Destillations- oder Extraktionssysteme, Laboratorien, Forschungsinstitute, chemische, pharmazeutische, petrochemische, biochemische, medizinische Einrichtungen, Krankenhäuser, F&E-Werkstätten, Halbleitertests, Luft- und Raumfahrt, biologische und andere Industrien.

Temperaturbereich Serie -25°C ~ -5°C Serie -45°C ~ -10°C Serie -60°C ~ -10°C Serie -80°C ~ -30°C Serie -110°C ~ -50°C Serie -150°C ~ -110°C
Kühlleistungbis zu 360 kWbis zu 360 kWbis zu 360 kWbis zu 270kWbis zu 180kWbis zu 11kW

 


Air Cooled Recirculating Chillers

Temperaturregelbereich: -120°C bis 30°C

Anwendung: Verschiedene Reaktoren, Destillations- oder Extraktionssysteme, Laboratorien, Forschungsinstitute, chemische, pharmazeutische, petrochemische, biochemische, medizinische Einrichtungen, Krankenhäuser, F&E-Werkstätten, Halbleitertests, Luft- und Raumfahrt, biologische und andere Industrien.

Temperaturbereich Serie -25°C ~ 30°C -45°C ~ 30°C Serie Serie -60°C ~ -20°C Serie -80°C ~ -20°C Serie -120°C ~ -70°C
Kühlleistungbis zu 38kWbis zu 12kWbis zu 7,2 kWbis zu 7,2 kWbis zu 8,6 kW

 


Normaltemperatur-Kühlgeräte

Temperaturregelbereich: +5°C bis +50°C

Anwendung: Verschiedene Reaktoren, Destillations- oder Extraktionssysteme, Laboratorien, Forschungsinstitute, chemische, pharmazeutische, petrochemische, biochemische, medizinische Einrichtungen, Krankenhäuser, F&E-Werkstätten, Halbleitertests, Luft- und Raumfahrt, biologische und andere Industrien.

Temperaturbereich -18°C ~ +30°C +5°C ~ +50°C Reihe
Kühlleistungbis zu 0,9 kWbis zu 50kW

Das Copyright liegt bei lneya-online.com, bitte kontaktieren Sie uns per E-Mail für weitere Informationen: lilia@lneya.com

Oder scannen Sie den unten stehenden WhatsApp- oder WeChat-QR-Code, um uns zu kontaktieren. 

WhatsAPP WeChat

scannen.

Vorherige: Nächste:
Kostenloses Angebot anfordern Plan

Laden...

购物车

X

我的足迹

X
Schlüsselwörter:Freude in Flaschen Kaltwassersatz