The Reason for the Increase in the Power Consumption of the Chiller

 

The cooling capacity of the chiller directly affects the operation of the entire system. For compressors with the same structure, the same speed, and the same refrigerant type, as the evaporating temperature decreases, the compression ratio of the compressor increases, and the energy consumption per unit of cooling capacity increases. So, what are the reasons for the increased power consumption when the chiller is running?

1. When the compressor is frosted, the small suction valve is quickly closed, the cooling capacity is sharply reduced, and the power consumption is relatively increased.

2. As the condensing temperature increases, the compression ratio of the compressor increases, and the energy consumption per unit cooling capacity increases. The condensing temperature is between 25°C and 40°C, and the power consumption increases by about 3.2% for every 1°C increase.

3. The surface of the evaporator is covered with a layer of frost, which reduces the heat transfer coefficient. In particular, the outer surface of the finned tube is frosted, which not only increases the heat exchange resistance, but also makes the air flow between the fins difficult, reducing the heat transfer coefficient and heat dissipation area.

4. When the heat exchange surfaces of the condenser and the evaporator are covered with an oil layer, the condensation temperature increases and the evaporation temperature decreases, resulting in a decrease in cooling capacity and an increase in power consumption. When a 0.1mm thick oil layer accumulates on the inner surface of the condenser, the cooling capacity of the compressor will decrease by 16.6, and the power consumption will increase by 12.4. When the oil is a 0.1mm thick inner surface evaporator, in order to maintain the predetermined low temperature requirement, the evaporation temperature is decreased by 2.5°C, and the power consumption is increased by 9.7.

5. When the air collects in the condenser, the pressure of the condenser will rise. When the partial pressure of the non-condensable gas reaches 1.96105Pa, the power consumption of the compressor needs to be increased by 18.

6. As the evaporation temperature decreases, the compression ratio of the compressor increases, and the unit energy consumption of production cooling increases. When the evaporation temperature is lowered by 1°C, it consumes 3% to 4%. Therefore, reducing the evaporation temperature difference as much as possible and increasing the evaporation temperature not only saves energy consumption, but also improves the relative humidity of the cold room.

7. When the size of the condenser wall reaches 1.5mm, the condensation temperature increases by 2.8°C, and the power consumption increases by 9.7.

8. The gas sucked by the compressor allows a certain degree of overheating, but if the overheating is too large, the specific volume of the sucked gas increases, the cooling capacity decreases, and the relative power consumption increases.

Nós somos um fabricante profissional de equipamento de controlo de temperatura, apoiando serviços personalizados, por favor consulte-nos para mais pormenores!

 


refrigerador de água de baixa temperatura

Refrigeradores de água

Gama de controlo de temperatura: -150°C a +50°C

 

 


sistema de arrefecimento e aquecimento

Sistemas dinâmicos de controlo da temperatura

Gama de controlo de temperatura: -120°C a +350°C

 

 

 


sistema de arrefecimento da bateria

Refrigeradores de teste para automóveis

Gama de controlo de temperatura: -40°C a +100°C

 

 

 


refrigerador de teste de semicondutores

Refrigeradores de teste de semicondutores

Gama de controlo de temperatura: -85°C a +250°C

 

 

 


congelador industrial

Frigoríficos industriais

Gama de controlo de temperatura: -150°C a -10°C

 

 

 

Os direitos de autor pertencem a lneya-online.com, por favor contacte o email para mais informações: lilia@lneya.com

Ou digitalize o código QR do WhatsApp ou WeChat abaixo para nos contactar. 

WhatsAPP WeChat

digitalização

Anterior: Seguinte:
Obter um orçamento gratuito Plano

carregando...

购物车

X

我的足迹

X
palavras-chave:Alegria engarrafada refrigerador de água