Pesquisar Pesquisar tudo

Start-Up Sequence of Screw Chiller

ClassificaçãoNotícias do sector 221

Start-Up Sequence of Screw Chiller

 

The start-up sequence of the screw chiller:

(1) Confirm whether the state of each relevant valve in the equipment meets the requirements of the specification. Supply power to the electrical control unit of the device and turn on the power switch to light up the electronically controlled lamps.

(2) When starting the cooling water pump, tower fan and refrigerant pump, you should be able to see the three running communication lights on. Fourth, check whether the oil temperature is above 30 ℃. When the temperature is lower than 30 ℃, the electric heater should be turned on for heating, and the oil pump can be started at the same time to make the circulating temperature rise evenly. After the oil pump is started, put the energy regulating control valve in the load reduction state, and make sure that the spool valve is in the zero position. Adjust the oil pressure regulating valve. Make the oil pressure reach 0.5~0.6MPa.

(3) Turn off the power of the amplifier, turn on the control switch, open the suction valve of the amplifier, and adjust the amplifier pressure after the delay of the start of the amplifier to make it higher than the exhaust pressure of 0.15~0.3MPa.

(4) Close the valve control circuit of the liquid supply in the liquid supply, start the valve of the liquid supply, put the energy regulating device in the loading position, and increase the loading with time. By adjusting the expansion valve, observe the suction pressure to stabilize the suction pressure between 0.36~0.56MPa. After the operation is completed, disconnect the power supply of the electric heater. When the temperature reaches 45 degrees Celsius, open the water inlet valve and the water outlet valve of the oil filler at the same time, so that the oil temperature is controlled between 40°C and 55°C when the oil filler is running. between.

(5) If the cooling temperature is low, the fan of the tower may be temporarily turned off. 1/2~1 turn on the fuel injection valve, and at the same time, the suction throttle and the equipment outlet throttle should be fully opened. Adjust the energy adjustment device to the 100% position, and adjust the expansion valve at the same time to keep the suction superheat temperature above 6°C.

(6) Check the startup of the screw elevator.

Nós somos um fabricante profissional de equipamento de controlo de temperatura, apoiando serviços personalizados, por favor consulte-nos para mais pormenores!

 


refrigerador de água de baixa temperatura

Refrigeradores de água

Gama de controlo de temperatura: -150°C a +50°C

 


sistema de arrefecimento e aquecimento

Sistemas dinâmicos de controlo da temperatura

Gama de controlo de temperatura: -120°C a +350°C

 

 


sistema de arrefecimento da bateria

Refrigeradores de teste para automóveis

Gama de controlo de temperatura: -40°C a +100°C

 

 


refrigerador de teste de semicondutores

Refrigeradores de teste de semicondutores

Gama de controlo de temperatura: -85°C a +250°C

 

 


congelador industrial

Frigoríficos industriais

Gama de controlo de temperatura: -150°C a -10°C

Os direitos de autor pertencem a lneya-online.com, por favor contacte o email para mais informações: lilia@lneya.com

Ou digitalize o código QR do WhatsApp ou WeChat abaixo para nos contactar. 

WhatsAPP WeChat

digitalização

Anterior: Seguinte:
Obter um orçamento gratuito Plano

carregando...

购物车

X

我的足迹

X
palavras-chave:Alegria engarrafada refrigerador de água