Changes in the Cooling Capacity of Industrial Chillers

ClassificaçãoNotícias do sector 178

Changes in the Cooling Capacity of Industrial Chillers

 

We often talk about the cooling capacity of the chiller. In fact, the nominal cooling capacity of the industrial chiller refers to the cooling capacity when the ambient temperature is 35°C and the chilled water outlet temperature is 7°C.

In actual operation, due to the different ambient temperature and chilled water outlet temperature, the cooling capacity of the industrial chiller and the power consumption of the compressor also vary. Whether it is an air-cooled chiller or a water-cooled chiller, its cooling capacity increases with the increase of the chilled water outlet temperature and decreases with the increase of the ambient air inlet temperature.

Why does this happen? This is because when the outlet temperature of the chilled water increases, the evaporation pressure of the corresponding industrial chiller increases, the suction specific volume decreases, and the refrigerating capacity per unit volume and the refrigerating capacity of the industrial chiller both increase; when When the ambient temperature increases, the condensing pressure in the refrigeration system of the industrial chiller increases. Since the evaporating temperature remains unchanged, its suction ratio volume also remains unchanged, the compressor air transmission coefficient of the chiller decreases, and the cooling capacity per unit mass decreases. , so the cooling capacity of industrial chillers is also reduced.

The power consumption of the industrial chiller increases with the increase of the outlet temperature of the chilled water, and increases with the increase of the ambient temperature. This is because the evaporation pressure increases when the chilled water temperature of the chiller increases. The pressure remains unchanged), the compression ratio is reduced, and the power consumption is reduced, but at this time, the power required to increase the cooling capacity of the industrial chiller is greater, so the total power consumption of the compressor is still increased.

If the ambient temperature increases and the condensing pressure increases, the chilled water outlet temperature of the industrial chiller remains unchanged (that is, the evaporative pressure remains unchanged), and the compression ratio increases and the power consumption increases. There is a reduction, but the total power consumption of the compressor still increases.

Nós somos um fabricante profissional de equipamento de controlo de temperatura, apoiando serviços personalizados, por favor consulte-nos para mais pormenores!

 


refrigerador de água de baixa temperatura

Refrigeradores de água

Gama de controlo de temperatura: -150°C a +50°C

 


sistema de arrefecimento e aquecimento

Sistemas dinâmicos de controlo da temperatura

Gama de controlo de temperatura: -120°C a +350°C

 

 


sistema de arrefecimento da bateria

Refrigeradores de teste para automóveis

Gama de controlo de temperatura: -40°C a +100°C

 

 


refrigerador de teste de semicondutores

Refrigeradores de teste de semicondutores

Gama de controlo de temperatura: -85°C a +250°C

 

 


congelador industrial

Frigoríficos industriais

Gama de controlo de temperatura: -150°C a -10°C

Os direitos de autor pertencem a lneya-online.com, por favor contacte o email para mais informações: lilia@lneya.com

Ou digitalize o código QR do WhatsApp ou WeChat abaixo para nos contactar. 

WhatsAPP WeChat

digitalização

Anterior: Seguinte:
Obter um orçamento gratuito Plano

carregando...

购物车

X

我的足迹

X
palavras-chave:Alegria engarrafada refrigerador de água