검색 모두 검색

Introduction of Expansion Valve in Industrial Chiller

분류업계 뉴스 209

Introduction of Expansion Valve in Industrial Chiller

 

In the chiller refrigeration system, the expansion valve is one of the four major components of the refrigeration system (compressor, condenser, expansion valve, evaporator).

The function of the expansion valve:

The expansion valve is one of the throttling devices. Its function in the refrigeration system of the chiller is to throttle the saturated liquid (or subcooled liquid) under the condensation pressure in the condenser or liquid receiver to the evaporation pressure and evaporate Temperature, while adjusting the flow of refrigerant entering the evaporator according to changes in load.

The composition of the expansion valve:ultra low temperature chiller - cryogenic chiller

Simply put, the expansion valve is composed of three parts: the valve body, the temperature sensor and the balance tube.
temperature sensor bag

The temperature-sensing bag is filled with refrigerant in a saturated gas-liquid equilibrium state, and this part of the refrigerant is not connected to the refrigerant in the system. It is generally tied to the outlet pipe of the evaporator, and is in close contact with the pipe to sense the temperature of the superheated steam at the outlet of the evaporator. Since the refrigerant inside it is saturated, it transmits the saturated state pressure to the valve body according to the temperature.

Balance tube

One end of the balance tube is connected to the outlet of the evaporator slightly away from the temperature-sensing bulb, and is directly connected to the valve body through a capillary tube. The function is to transmit the actual pressure at the outlet of the evaporator to the valve body. There are two super-large industrial fans with diaphragms in the valve body, and the diaphragms move upward under the action of pressure to reduce the refrigerant flow through the expansion valve, seeking balance in dynamics.

Quality judgment

Generally speaking, the higher the degree of superheat set by the thermal expansion valve, the lower the heat absorption capacity of the evaporator, because increasing the degree of superheat will take up a considerable part of the heat transfer surface of the evaporator, so that the saturated steam can be superheated here. It occupies a part of the heat transfer area of the evaporator, so that the area of the refrigerant vaporizing and absorbing heat is relatively reduced, that is to say, the surface of the evaporator is not fully utilized. However, if the degree of superheat is too low, the refrigerant liquid may be brought into the compressor, causing the unfavorable phenomenon of liquid hammer.

Therefore, the superheat adjustment of the expansion valve should be appropriate, which can not only ensure that enough refrigerant enters the evaporator, but also prevent liquid refrigerant from entering the compressor. When the resistance of the refrigerant flowing through the evaporator is small, it is best to use an internally balanced thermal expansion valve. Conversely, when the resistance of the evaporator is large, generally exceeding 0.03MPa, an externally balanced thermal expansion valve should be used.

우리는 온도 제어 장비의 전문 제조업체로 맞춤형 서비스를 지원합니다. 문의하기 자세한 내용을 확인하세요!

 


자동차 테스트 냉각기

온도 제어 범위: -40°C ~ +100°C

 

제품 보기

 


반도체 테스트 냉각기

온도 제어 범위: -85°C ~ +250°C

 

제품 보기

 


산업용 냉장고

온도 제어 범위: -150°C ~ -10°C

 

제품 보기

 

저작권 정보는 lneya-online.com에 귀속되며 자세한 내용은 이메일로 문의하시기 바랍니다: lilia@lneya.com

또는 아래의 WhatsApp 또는 WeChat QR 코드를 스캔하여 문의하세요. 

왓츠앱 위챗

스캔

이전: 다음:
무료 견적 요금제 받기

로딩 중...

购物车

X

我的足迹

X
키워드: 키워드병에 담긴 기쁨 물 냉각기