First, chemical circulating chiller oil pressure difference alarm

One is long-term operation under low load conditions, an alarm will occur to keep the unit running at full load. There is also an alarm when the cooling water temperature is lower than 20 ℃, and it is difficult to maintain the oil supply by the pressure difference. Let’s talk about the situations in which the oil pressure difference fails. First, the heat exchanger or oil pressure sensor fails, which needs to be calibrated and replaced. The second is that the internal and external filters are blocked, and a new filter should be replaced. The third is the failure of the oil supply solenoid valve, check the coil.

Second, the high and low pressure alarm of the suction pressure of the chemical circulating chiller

It may be that the low pressure sensor is out of order or has poor contact, or it may be that the refrigerant is insufficient or leaking, or the drying filter may be blocked. Just disassemble and clean it. When the opening of the expansion valve is small, damage to the motor or poor contact will also cause a low pressure alarm. What about the exhaust pressure high pressure alarm? It may be that the cooling water valve is not open or the flow rate is insufficient; it may also be that the copper pipes in the condenser are seriously fouled, and the copper pipes need to be cleaned. It may also be that there is non-condensable gas in the unit, and it should be discharged in time and evacuated.

Third, the abnormal sound of the compressor of the chemical circulating chiller

First see if the main fuel supply valve is closed, you need to open it! Then the coupling is not loose! Then see if there is a liquid shock, and the screw compressor will also have a liquid shock. Adjust it quickly, otherwise it will damage the compressor and cause damage to the bearing, especially the reciprocating compressor, which is deadly. Just replace the compressor or replace it with a new device. Also check if the bearing is worn out and report for repair in time.

We are a professional manufacturer of temperature control equipment, supporting customized services, please consult us for details!

 


Water Chillers

Temperature Control Range: -150°C to +50°C

 

View Products

 


Dynamic Temperature Control Systems

Temperature Control Range: -120°C to +350°C

 

View Products

 


Automobile Test Chillers

Temperature Control Range: -40°C to +100°C

 

View Products

 


Semiconductor Test Chillers

Temperature Control Range: -85°C to +250°C

 

View Products

 


Industrial Refrigerators

Temperature Control Range: -150°C to -10°C

 

View Products

Copyright information belongs to lneya-online.com, please contact email for details: lilia@lneya.com

Or scan the WhatsApp or WeChat QR code below to contact us. 

WhatsAPP                                   WeChat

scan

Previous: Next:
Get Free Quote Plan

loading...

购物车

X

我的足迹

X
keywords:< a href="https://lneya-online.com/sitemap.html" title="water chiller"target="_blank">Bottled joy < a href="https://lneya-online.com/sitemap.xml" title="water chiller"target="_blank">water chiller